Commercial AV System — Annual Compliance Test Report

Site
Conference Centre, Nelson (fictional)
Date of test
15 July 2024
Technician
T. Smythe — TS Tech Consult
Standard
AS/NZS 3000:2018 (Wiring Rules), AS 2293.1 (Emergency Lighting)

Scope

Annual electrical safety and performance compliance test of the installed AV system across the main conference room (Room A), breakout rooms (B, C) and ballroom. The test covers mains distribution, speaker circuit impedance, emergency-stop functionality, and DSP preset recall.

Test Equipment

InstrumentModelCalibration due
Multifunction testerMegger MFT1741March 2025
SMAART measurement rigRational Acoustics SMAART v9N/A (software)
Sound level meterNTi Audio XL2January 2025
Network cable certifierFluke DSX-8000June 2025

Test Results

Test pointLocationMeasuredLimitResult
Earth continuityRack PDU-10.08 Ω< 0.5 ΩPass
Insulation resistanceRoom A speaker circuit> 200 MΩ> 1 MΩPass
RCD trip time (30 mA)Rack DB22 ms< 300 msPass
Emergency stopRoom A wall panelImmediate muteImmediate mutePass
DSP preset recallBallroom mode 3CorrectMatches baselinePass
SPL at FOH (pink noise)Ballroom94.2 dBAN/A (ref only)Info
Network cable cert.Dante primary linkClass EAClass EAPass

Notes

All circuits tested within specification. The emergency-stop button in Room A was cleaned (dust ingress on the NC contact) during testing — no fault found, preventive only. Recommended: re-test emergency-lighting battery packs within six months (not in scope of this AV-specific test).